Fibre Glass Cable & Lead Wire

Fibre Glass Cables are tear resistant due to uniaxial orientation. The multiple layer construction of Mylar insures high dielectric strength insulation. Thin cross sections of Mylar 0.0004" to .007" thick ensures greater cut through. They are specifically designed to bear high temperatures. They are used in motor connecting leads.

Maximum Current Ratings (Amp.)

Nominal Area No. & Dia of Wire Max. Conductor Resistance at 20°C  Radial Thickness of Insulation Max. Overall Diameter Delivery Length in Coil
mm2 (mm) (Ohms/km.) (mm) (mm) (mtrs)
0.5 16/0.20 38.2 0.4 1.9 100
0.75 24/0.20 25.4 0.45 2.2 100
1 32/0.20 19.1 0.45 2.4 100
1.5 30/0.25 13 0.45 2.6 100
2.5 50/0.25 7.82 0.5 3.4 100
4 80/0.25 4.85 0.55 4 100
6 120/0.25 3.23 0.55 5 50
10 80/0.40 1.85 0.6 6 50
16 126/0.40 1.18 0.7 7.2 50
25 196/0.40 0.757 0.7 9 50
35 276/0.40 0.538 0.8 11 50

Maximum Current Ratings (Amp.)

Size At 105°C Working Temperature At 130°C Working Temperature
mm2 Continuous 5 Minutes 1 Minute Continuous 5 Minutes 1 Minute
0.5 12 15 18 8 10 12
0.75 15 19 22 10 13 16
1 18 22 27 13 15 18
1.5 22 26 33 17 20 26
2.5 32 38 50 21 36 32
4 45 55 75 30 38 45
6 62 72 110 38 49 62
10 90 105 175 60 72 90
16 125 162 260 80 100 125
25 175 230 400 110 140 175
35 210 315 555 140 170 215